Bitmain DCRACK: 47U cabinet for air-cooled servers with an outdoor heat-pump cooler, 36 kW maximum load, 380–415 V three-phase.

$19,000

Ships in 5–10 business days

$19,000Free standard shipping. Excludes duties and taxes

Description

DCRACK is Bitmain's single-cabinet system for air-cooled servers: a 47U server cabinet with three fans, paired with an external heat-pump cooler (R410A refrigerant, with its own refrigerant pump) that can stand up to 50 m away. It handles up to 36 kW of load and supplies 18–27 °C air to the servers.

Specifications

  • Capacity: 47U; maximum load 36 kW
  • PUE: 1.17 at 25 °C ambient and 25 °C supply air (without water curtain)
  • Server supply air temperature: 18–27 °C
  • Cabinet: 1,600 × 1,200 × 2,350 mm; 668 kg net
  • Cabinet supply: 380–415 V AC, three-phase, 50/60 Hz, 63 A maximum
  • Network: RJ45 Ethernet 10/100M
  • Cabinet fans: 3; rated power 2,500 W; 85 dBA at 1 m
  • External cooler: 1,896 × 1,026 × 2,180 mm; 396 kg net
  • Cooler supply: 380–415 V AC, three-phase, 50/60 Hz, 63 A maximum
  • Heat pump: 8.5 kW rated power, COP 4.75 typical, R410A
  • Cooler fans: 2; rated power 1.85 kW; 82 dBA at 1 m
  • Refrigerant pump: 550 W, 1 m³/h, 48 m head
  • Ambient temperature: -20 to 45 °C
  • Storage: -20 to 70 °C; humidity 10–90% RH non-condensing

Notes

  • Wrong input voltage can damage the equipment.
  • Installation must be carried out by a qualified electrician to local code.