AvailableCondition: New
DCRACK
- Manufacturer
- Bitmain
Bitmain DCRACK: 47U cabinet for air-cooled servers with an outdoor heat-pump cooler, 36 kW maximum load, 380–415 V three-phase.
$19,000
Ships in 5–10 business days
$19,000Free standard shipping. Excludes duties and taxes
Description
DCRACK is Bitmain's single-cabinet system for air-cooled servers: a 47U server cabinet with three fans, paired with an external heat-pump cooler (R410A refrigerant, with its own refrigerant pump) that can stand up to 50 m away. It handles up to 36 kW of load and supplies 18–27 °C air to the servers.
Specifications
- Capacity: 47U; maximum load 36 kW
- PUE: 1.17 at 25 °C ambient and 25 °C supply air (without water curtain)
- Server supply air temperature: 18–27 °C
- Cabinet: 1,600 × 1,200 × 2,350 mm; 668 kg net
- Cabinet supply: 380–415 V AC, three-phase, 50/60 Hz, 63 A maximum
- Network: RJ45 Ethernet 10/100M
- Cabinet fans: 3; rated power 2,500 W; 85 dBA at 1 m
- External cooler: 1,896 × 1,026 × 2,180 mm; 396 kg net
- Cooler supply: 380–415 V AC, three-phase, 50/60 Hz, 63 A maximum
- Heat pump: 8.5 kW rated power, COP 4.75 typical, R410A
- Cooler fans: 2; rated power 1.85 kW; 82 dBA at 1 m
- Refrigerant pump: 550 W, 1 m³/h, 48 m head
- Ambient temperature: -20 to 45 °C
- Storage: -20 to 70 °C; humidity 10–90% RH non-condensing
Notes
- Wrong input voltage can damage the equipment.
- Installation must be carried out by a qualified electrician to local code.

Wholesale & project supply
Building or expanding a mining operation?
Bulk ASIC procurement for mining farms, hosting companies, resellers and institutional operators. Send model, quantity and destination; sales replies with pricing and lead time.