Work out the voltage, current, circuit capacity and connectors a Bitcoin miner needs before you order it, so you can brief your electrician.

Published October 1, 2026 · Reviewed by James Emerson

A full-size air-cooled Bitcoin miner is a continuous load of roughly 3 to 4 kW on a 200–240 V class single-phase supply. Hydro and immersion machines are usually three-phase loads of 5 kW or more. To power one safely you need a supply voltage inside the model's published input range, a circuit sized for the current it draws around the clock, the right connector, and a sound earth connection.

Everything here is for planning and for briefing an electrician. Mains wiring, breaker sizing and three-phase distribution must be designed and installed by a qualified electrician to your local code.

Key points

  • Current (A) = power (W) ÷ voltage (V) for single-phase, and power ÷ (√3 × line-to-line voltage) for three-phase.
  • A miner runs 24 hours a day, so it is a continuous load. Under North American practice a continuous load may use only 80% of the breaker rating.
  • Size for the published power plus its tolerance, not the typical figure.
  • Standard 110–120 V outlets cannot run a full-size miner.
  • Check the exact model's published voltage range, phase and input current. They differ between models.

Watts, volts and amps

  • Watts (W) measure power, the rate at which the machine uses energy. This is what you pay for and what becomes heat.
  • Volts (V) measure the supply voltage.
  • Amps (A) measure current. Current determines the size of the wire, breaker and connector.

They are related by:

single-phase:  P = V × I × PF          so  I = P ÷ (V × PF)
three-phase:   P = √3 × V(line-to-line) × I × PF

PF is power factor, the ratio of real power to voltage multiplied by current. The examples assume PF ≈ 1, a reasonable approximation for power supplies with active power-factor correction. If the manufacturer publishes a lower figure, the current is slightly higher.

A miner's power supply draws roughly constant power, so the same machine needs more amps on 208 V than on 240 V.

Current for a single-phase miner

Illustrative machine: 3,500 W, single-phase, PF ≈ 1. The third column adds a 5% power tolerance (3,675 W), which is the figure to design around.

Supply voltage Current at 3,500 W Current at 3,675 W 3,675 W current ÷ 0.8
208 V 16.83 A 17.67 A 22.09 A
230 V 15.22 A 15.98 A 19.97 A
240 V 14.58 A 15.31 A 19.14 A

The last column is the minimum breaker rating that keeps the load at or below 80%, which applies under North American practice. On calculated current, the machine at 240 V fits within the 16 A continuous capacity of a 20 A circuit. At 208 V it does not, and it needs the next size up. A 230 V supply outside North America is sized by that country's rules instead.

Calculated current is a planning figure. Manufacturers also publish an input current, and it can be higher. Bitmain lists a 20 A AC input for the Antminer S21, a 3,500 W machine. If the electrician sizes on that published figure, the minimum breaker is 20 ÷ 0.8 = 25 A, which in practice means a 30 A circuit. The nameplate and the manufacturer's documentation decide the circuit, not this table.

Current for a three-phase miner

Illustrative machine: 5,500 W, three-phase, PF ≈ 1. The current shown flows in each of the three line conductors.

Line-to-line voltage Current at 5,500 W Current at 5,775 W (+5%)
400 V 7.94 A 8.34 A
415 V 7.65 A 8.03 A
480 V 6.62 A 6.95 A

Worked for 400 V: 5,500 ÷ (1.732 × 400) = 7.94 A. The 480 V row applies only to models whose published input range includes 480 V. Many three-phase machines are limited to 380–415 V. See Three-Phase Mining Equipment.

Breakers and the 80% continuous-load rule

A breaker protects the wiring from overheating. It is chosen for the circuit, and the circuit is chosen for the load.

North American codes treat a load that runs at maximum current for three hours or more as continuous, and commonly limit it to 80% of the breaker rating unless the equipment is specifically rated for 100% continuous duty. A miner is continuous by any definition.

Breaker rating Continuous limit (80%) Usable power at 208 V Usable power at 240 V
20 A 16 A 3,328 W 3,840 W
30 A 24 A 4,992 W 5,760 W
40 A 32 A 6,656 W 7,680 W
50 A 40 A 8,320 W 9,600 W

Usable power is the continuous limit multiplied by the voltage, for a single-phase circuit. Other regions follow their own codes, which typically size the circuit from the design current, the cable type and the installation method rather than a flat 80%. In every case the decision belongs to the electrician and the local code.

Cable sizing as a concept

A conductor's safe current, its ampacity, must be at least the rating of the breaker protecting it. Ampacity is not a single number for a given wire size. It depends on:

  • conductor material and cross-section;
  • the temperature rating of the insulation;
  • ambient temperature, which is high in a room full of miners;
  • how many loaded cables are bundled or share a conduit or tray;
  • the installation method.

Heat and bundling both reduce allowable current, and mining installations have plenty of both. Long runs add a further check for voltage drop. The cord between the PDU and the miner is part of the circuit too: it must be rated for the miner's current and for the protection upstream of it.

Why 110–120 V circuits are unsuitable

Two separate reasons rule out an ordinary North American wall outlet for a full-size miner.

  1. Current. 3,500 W at 120 V is 29.17 A. A 15 A circuit carries 12 A continuously (1,440 W) and a 20 A circuit carries 16 A (1,920 W).
  2. Input range. The power supplies are not designed for it. Bitmain publishes an input range of 220–277 V for the Antminer S21, and MicroBT publishes 220–240 V for the WhatsMiner M60S+. Both are manufacturer-published figures.

A step-up transformer on a wall outlet does not help. It changes the voltage, not the power, so the 120 V side would still need to supply more than 29 A.

The exception is the class of small, low-power home miners built for household outlets. Check the published input range for the specific unit. For full-size machines in North America, see 220V Bitcoin Mining.

PDUs and connector types

A PDU (power distribution unit) takes one larger feed and splits it into several outlets, usually with a breaker per outlet or per bank and sometimes with metering. It is where the branch protection for each miner's cord normally sits.

Most air-cooled miners use IEC 60320 appliance connectors:

Connector pair IEC current rating Typical use
C13 (cord) / C14 (inlet) 10 A Lower-power equipment, and miners that split their load across two inputs
C19 (cord) / C20 (inlet) 16 A Full-size miners with a single high-current input

North American certifications assign these connectors somewhat higher ratings than the IEC figures. Use the rating marked on the actual cord and outlet.

Published examples: MicroBT's datasheet for the WhatsMiner M60S+ specifies an IEC C19 cable rated at least 16 A. Bitmain's specification for the Antminer S19k Pro lists two AC inputs at 10 A each, and its Antminer S21 specification lists one at 20 A.

Hydro and immersion machines are different. They are three-phase units and generally do not use C13 or C19 cords. Expect manufacturer-specific power connectors or cables terminated directly onto a PDU, busbar or terminal block. MicroBT's WhatsMiner M63S++ datasheet describes its power cable as custom made and rated at least 16 A, and Bitmain lists an LP34 power port on its rack-format U3S23H hydro unit. Use the manufacturer's cable set and have terminations made by an electrician.

See PDUs and power cables.

Power quality and grounding

  • Voltage under load. Measure at the miner with everything running. A supply that reads 240 V unloaded and sags under load pushes current up and can fall outside the published range.
  • Frequency. Published ranges cover 50 and 60 Hz supplies. Generator-fed sites need stable frequency and voltage regulation.
  • Grounding. Every miner, PDU and rack must be connected to protective earth so that a fault trips the protection instead of energising the metalwork. Never use an adapter or cord that removes the earth connection.
  • Connections. A slightly loose plug or terminal carrying 15 A around the clock will overheat. Discoloured plugs and warm connectors are warnings to act on.
  • Surges and harmonics. Larger sites need surge protection and a distribution design that accounts for harmonic currents. This is engineering work for the site's electrical designer.

Do not bypass or oversize protection to stop a breaker from tripping. A trip means the circuit is overloaded or faulty.

Planning steps

  1. Find the published power, voltage range, phase and input current for the exact model and hashrate version.
  2. Add the published power tolerance.
  3. Calculate current at your actual supply voltage.
  4. Give those figures to a qualified electrician to size the circuit, breaker and cable to local code.
  5. Confirm the connector on the miner and order matching cords and PDU outlets.
  6. Plan heat removal. Every kilowatt the miner draws becomes about 3,412 BTU/h of heat.